Item
|
Specification
|
Enclosure
|
Mounted in a panel
|
Grounding method
|
Ground to 100 Ω or less
|
Operating environment
|
Ambient operating temperature
|
0 to 55°C
|
Ambient operating humidity
|
10% to 95% RH (with no condensation or icing)
|
Atmosphere
|
Must be free from corrosive gases.
|
Ambient storage temperature
|
−25 to 70°C (with no condensation or icing)
|
Altitude
|
2,000 m max.
|
Pollution degree
|
Pollution degree 2 or less: Conforms to JIS B 3502 and IEC 61131-2.
|
Noise immunity
|
Conforms to IEC 61000-4-4, 2 kV (power supply line)
|
Overvoltage category
|
Category II: Conforms to JIS B 3502 and IEC 61131-2.
|
EMC immunity level
|
Zone B
|
Vibration resistance
|
Conforms to IEC 60068-2-6.
5 to 8.4 Hz with amplitude of 3.5 mm,
8.4 to 150 Hz, acceleration of 9.8 m/s2
100 min each in X, Y, and Z directions (10 sweeps of 10 min each = 100 min total)
|
Shock resistance
|
Conforms to IEC 60068-2-27. 147 m/s 2 , 3 times each in X, Y, and Z directions
|
Insulation resistance
|
20 MΩ min. between isolated circuits (at 100 VDC)
|
Dielectric strength
|
510 VAC between isolated circuits for 1 minute at a leakage current of 5 mA max.
|
Applicable standards
|
cULus: Listed (UL 61010-2-201), ANSI/ISA 12.12.01,
EU: EN 61131-2, RCM, KC: KC Registration, EAC
|